Reverse cleaning conditions for reverse osmosis membrane repair

Sep 28,2018

Reverse osmosis offline cleaning conditions:

1. When the single-stage pressure difference of the reverse osmosis system is greater than twice the single-stage pressure difference at the beginning of the system operation.

2. The water production of reverse osmosis system drops by more than 30%.

3. The weight of a single reverse osmosis membrane element exceeds the normal value of 3 kg or more.

4. The reverse osmosis system cannot be recovered by online cleaning performance.

Offline cleaning step of reverse osmosis membrane

1. First replace the membrane element to be cleaned on the reverse osmosis system with a spare membrane element with excellent performance to ensure that the reverse osmosis system does not stop running and ensure the continuous stability of the entire production process.

2. Test the performance of reverse osmosis membrane components:

3. Understand the current operating status of the system before cleaning the system; collect the parameters of the running reverse osmosis system and make the original records.

4. Judging the cleaning process based on the user's original water analysis report, performance test results, and the system information that is known.

5. Identification of pollutants. Firstly, according to the analysis results of 3.4, preliminary judgments are made, and further verification is carried out by special equipment and instruments to determine the specific pollutant type.

6. According to the analysis results, determine the required cleaning formula and concentration.

7. Perform the experimental cleaning on the reverse osmosis special cleaning equipment with the above cleaning agent combination cleaning means to select the appropriate cleaning formula and cleaning procedure.

8. Determine the cleaning method and treat all of the above membrane elements.

9. The cleaned membrane element enters the test platform for testing and recording. If it does not meet the requirements, it will be sent back to the cleaning equipment for processing.

 

More inquiries pl contact 

KHN water treatment equipments Co., Ltd.                             www.khnwatertreatment.com


Send Inquiry

Contact Us

  • Add:No.26 Chuangye Road Heqiao Town Yixing City Jiangsu China
  • Tel:+86-510-87877760
  • Fax:+86-510-87877760
  • Ph:+8617751526380
  • E-mail:sales@khnwatertreatment.com

QR Code

Copyright © Wuxi Deiichen Machinery Pty.,Ltd. All Rights Reserved.